Optional registry entries for WEBfactory 2010 Server
Check out this article and learn more details about optional registry entries for WEBfactory 2010 Server.
The following registry entries are now available for WEBfactory 2010 Server, at the specified location:
[HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\WEBfactory\WFServer\2.00\Settings]:
"SO_Tracing"="1"
"SO_TraceFile"="d:\\wflog2\\SOLog"
"SO_TraceFileSize"="100000000"
"DisableOPCItemValidation"="1
Registry entries details
SO_Tracing: Softing Tracing allows to trace the OPC-Client communication to the WEBfactory 2010 Server. If SO_Tracing is set to 1 the tracing is activated
SO_TraceFile: SO_TraceFile sets the location where the file is placed. The target folder must exist!
SO_ TraceFileSize: SO_ TraceFileSize sets the size of the files in Bytes. Softing always holds two files of this size.
DisableOPCItemValidation: If DisableOPCItemValidation set to 1, the Server doesn't check each OPC-Item if it is valid in OPC-Server. This could speed up the start-up time for systems with slow working OPC-Servers. For example, OPC-Severs that handle serial line communication will start up much faster.